Client-side 1+1 protection uses two wavelengths: one is the working wavelength, and the other is the protection wavelength. The two wavelengths adopt diverse routing to transmit signals to protect the OTU and the OCh fibers.
The trigger conditions for the client 1+1 protection automatic switching are as follows:
In the case of the OptiX OSN 3800A/6800A/8800 T16 (NA)/8800 T32 (NA)/8800 T64 (NA):
IN-PWR-HIGH and IN-PWR-LOW are valid for LWXS board.
In the case of the OptiX OSN 1800 (NA):
Client-side 1+1 protection is in three types.
This protection is utilized when the working OTU and the protection OTU are in the same subrack of an NE. The SCS board is recommended for this type of protection.
This protection is utilized when the working OTU and the protection OTU are in different subracks of an NE. The OLP or DCP board must be used for this type of protection.
This protection is utilized when the working OTU and the protection OTU are in different NEs. The OLP or DCP board must be used for this type of protection.
In the case of the OptiX OSN 6800A/3800A, the client 1+1 protection and VLAN SNCP cannot be configured at the same time for the L4G and TBE board.
The three types share similar protection principles. The difference lies in that the positions of the working and protection OTU boards are different.
When the SCS board is used, the system selects signals by enabling or disabling the client-side laser of the working or the protection OTU board. When the OLP or DCP board is used, the client-side lasers of the working and protection OTU boards are enabled. In this case, the system selects signals by using the SCC board to control the OLP or DCP board. Figure 1shows the principle with the client 1+1 protection as an example.
For the description of the working principle of the SCS, OLP and DCP boards, refer to the Hardware Description.

: Direction of the working signal flow |
: Direction of the protection signal flow |