Environment Monitoring Interface

In this user interface, you can query and configure the interface parameters for environment monitor interface.

Navigation Path

In the NE Explorer, select a board and choose Configuration > Environment Monitoring Configuration > Environment Monitoring Interface from the Function Tree.

Parameters

Field

Value

Description

Operation Object

NE name-slot number-board name

Displays the environment monitoring board.

Basic Attributes

Operation Object

NE name-slot number-board name

Displays the environment monitoring board.

Relay Control Mode

Auto Control, Manual Control

There are two options: Auto Control and Manual Control. In Auto Control mode, the corresponding alarm relay will be automatically opened when an alarm occurs and closed if there is no alarm. In Manual Control mode, you need to set the status of alarm relay K0 and K1. K0 is the minor alarm switching and K1 is the critical alarm switching.Relay Status in Major Alarm(K0) and Relay Status in Critical Alarm(K1).

Relay Status in Major Alarm (K0)

Enabled, Disabled

Displays the switching selection for common alarm relay. The relay is turned on when the option is selected, and off when the option is not selected. It can be set only when the alarm relay is manually controlled.

Relay Status in Critical Alarm (K1)

Enabled, Disabled

Displays the switching selection for critical alarm relay. The relay is turned on when the option is selected, and off when the option is not selected. It can be set only when the alarm relay is manually controlled.

Input Relay

Using Status

Used, Unused

Sets the use status of the input relay.

Path Name

For example: CSK-1

Sets the path name of input and output path.

Alarm Mode

Relay Turns Off, Relay Turns On

  • If this parameter is set to Relay Turns On, the alarm is generated when the relay is on.
  • If this parameter is set to Relay Turns Off, the alarm is generated when the relay is off.

Alarm Severity

Critical Alarm, Major Alarm, Minor Alarm, Warning Alarm

Sets the alarm severity for the input relay.

Output Relay

Use or Not

Used, Unused

Displays the status of the output relay, which can be Used or Unused.

Path Name

For example: CSK-1

Sets the path name of input and output path.

Working Mode

Auto Working Mode, Manual Working Mode

Sets the working mode, which can be Auto Working Mode or Manual Working Mode.

  • Automatic: Changing the status of the output relay according to Alarm Trigger Conditions and Alarm Mode
  • Manual: Determining the status of the output relay manually

Alarm Trigger Conditions

Auto Working Mode
  • Value: Input Path 1-Input Path 6, Automatically Triggered by Major Alarms, Automatically Triggered by Critical Alarms, Automatically Triggered by Critical and Major Alarms
  • Default: Automatically Triggered by Critical and Major Alarms

Automatically changing the status of the relay according to the preset value.

Manual Working Mode
  • Value: Output Low Level in Manual and Output High Level in Manual
  • Default: Output High Level in Manual

Outputting the high level or low level according to the setting.

Alarm Mode

Alarm Occurs when Relay Turns Off, Alarm Occurs when Relay Turns On

Default: Alarm Occurs when Relay Turns Off

  • If this parameter is set to Alarm Occurs when Relay Turns Off, the alarm is generated when the relay is off.
  • If this parameter is set to Alarm Occurs when Relay Turns On, the alarm is generated when the relay is on.

Alarm Relay

Alarm Severity

Critical Alarm, Major Alarm, Minor Alarm, Warning Alarm

Displays the alarm severity for the alarm relay.

Alarm Output Channel

For Example: CSK-1

Displays the alarm output channel.

Relay Control Mode

Auto Control, Manual Control

Sets the control mode of the alarm relay.

Alarm Relay Status

On, Off

Sets the status of the alarm relay. This parameter can be edited in the Manual Control mode only.

Temperature Attributes

Operation Object

NE name-slot number-board name

Displays the environment monitoring board.

Monitor Status

Monitor, No Monitor

Sets monitor status of the temperature attributes.

Temperature Upper Threshold (DEG.C)

For example: 65.0

Displays the upper temperature threshold. When the actual temperature is higher than this threshold, a temperature alarm is generated.

Temperature Lower Threshold (DEG.C)

For example: 0.0

Displays the lower temperature threshold. When the actual temperature is lower than this threshold, a temperature alarm is generated.

Outdoor cabinet interface

Operation Object

For example: NE1-11-PMU

Indicates the operation object.

Number of PSUs

For example: 1

Indicates the number of PSUs.

Control Status

Master node control, Automatic slave node control

Specifies the control status.

Recharge mode

Evenly recharge, Floating recharge

Specifies the charging mode of the battery.

This parameter is available only when you set Control Status to Master node control.

Battery recharging current-limit coefficient

0.05 to 0.25

Specifies the current-limit coefficient for battery recharging.

Battery group number

For example: 1

Specifies the battery group number.

Battery group capacity (AH)

5 to 1000

Specifies the capacity of a battery group.

Battery group temperature (°C)

For example: 15

Indicates the temperature of a battery group.

High temperature threshold for alarm (°C)

35 to 80

Specifies the upper threshold for the temperature of a battery group.

When the temperature of a battery group exceeds this threshold, an alarm is reported.

Low temperature threshold for alarm (°C)

-20 to 20

Specifies the lower threshold for the temperature of a battery group.

When the temperature of a battery group is lower than this threshold, an alarm is reported.

Battery scheduled evenly-recharge duration (day)

30 to 240

Specifies the scheduled evenly-recharging duration for a battery.

Battery temperature compensation coefficient (°C/0.001V)

0 to 500

Specifies the temperature compensation coefficient of a battery group.

Bus bar voltage (V)

For example: 48

Indicates the voltage of a bus bar.

Total load current

For example: 5

Indicates the total load current.

Current of storage battery group 1

For example: 3

Indicates the current of battery group 1.

Current of storage battery group 2

For example: 2

Indicates the current of battery group 2.

AC voltage (V)

For example: 48

Indicates the value of the AC voltage.

Current-limit state

Enabled, Disabled

Enables or disables the current-limit function.

Floating-recharge conversion state

  

Indicates the control status of the floating-recharge conversion.

Recharge state

  

Indicates the current recharging status.

Battery power-down state

Enabled, Disabled

Enables or disables the battery power-off function.

Number of power modules

For example: 2

Indicates the number of power modules.

Relevant Humidity

For example: 50%

Indicates the humidity of the environment.

Outdoor cabinet PMU electrical source system attribute

Operation Object

For example: NE1-11-PMU

Indicates the operation object.

High AC voltage alarm threshold (V)

61 to 300

Specifies the upper threshold for the AC voltage.

When the AC voltage exceeds this threshold, an alarm is reported.

Low AC voltage alarm threshold (V)

60 to 299

Specifies the lower threshold for the AC voltage.

When the AC voltage is lower than this threshold, an alarm is reported.

High DC voltage alarm threshold (V)

58.0 to 60.0

Specifies the upper threshold for the DC voltage.

When the DC voltage exceeds this threshold, an alarm is reported.

Low DC voltage alarm threshold (V)

35.0 to 55.6

Specifies the lower threshold for the DC voltage.

When the DC voltage is lower than this threshold, an alarm is reported.

Evenly-recharged voltage (V)

43.2 to 57.6

Indicates the voltage of an even recharging.

Floating-recharged voltage (V)

43.2 to 57.6

Indicates the voltage of a floating recharging.

Batter power-down enabling state

Enabled, Disabled

Enables or disables the load power-off function.

Battery power-down voltage threshold (V)

35.0 to 55.3

Specifies the load power-off voltage.

When the load voltage exceeds this value, a powered off occurs.

Battery group power-down enabling state

Enabled, Disabled

Enables or disables the power-off function for a battery group.

Battery group power-down voltate threshold (V)

35.0 to 55.3

Specifies the power-off voltage for a battery group.

When the voltage of a battery group exceeds this value, a powered off occurs.

Enabling state on high temperature of battery group

Enabled, Disabled

Enables or disables the power-off function due to high temperature.

Battery group power-down terperature (°C)

40 to 70

Specifies the temperature for power-off due to high temperature.

When the temperature exceeds this value, a powered off occurs.

Outdoor cabinet PMU alarm threshold

Operation Object

For example: NE1-11-PMU

Indicates the operation object.

Threshold type

Ambient temperature (°C), Ambient humidity (%)

Indicates the causes of an alarm.

Upper threshold

35 to 80 for Ambient temperature (°C)

50 to 100 for Ambient humidity (%)

Specifies the upper threshold for reporting alarms.

When the value of Threshold type exceeds this threshold, an alarm is reported.

Lower threshold

-20 to +20 Ambient temperature (°C)

0 to 50 for Ambient humidity (%)

Specifies the lower threshold for reporting alarms.

When the value of Threshold type is lower than this threshold, an alarm is reported.

Outdoor cabinet ambient temperature

Operation Object

For example: NE1-11-PMU

Indicates the operation object.

Sensor number

For example: 1

Indicates the sensor number.

Ambient temperature (°C)

For example: 25.6

Indicates the ambient temperature.

Outdoor cabinet interface

Operation Object

For example: NE1-12-TCU

Indicates the operation object.

Environment temperature (°C)

For example: 49

Indicates the temperature of the temperature control unit.

Temperature of rack outlet (°C)

For example: 48

Indicates the temperature of the air exhaust vent of a rack.

Temperature of rack inlet (°C)

For example: 20

Indicates the temperature of the air intake vent of a rack.

Average speed of internal circulation fan (RPM)

For example: 1000

Indicates the average speed of an internal circulation fan.

Average speed of external circulation fan (RPM)

For example: 1000

Indicates the average speed of an external circulation fan.

Work mode

Temperature control speed adjustment, Master control fan speed grade, Master control fan percent

Specifies the mode of adjusting the fan speed.

Fan speed grade attribute

Fixation high speed, Fixation low speed

Specifies the parameters of speed adjustment in the discrete speed adjustment mode.

This parameter is available when you set Work mode to Master control fan speed grade.

Speed of internal circulation fan (RPM)

20 to 100

Specifies the speed of an internal circulation fan in the duty ratio mode.

This parameter is available only when you set Work mode to Master control fan percent.

Speed of external circulation fan (RPM)

20 to 100

Specifies the speed of an external circulation fan in the duty ratio mode.

This parameter is available only when you set Work mode to Master control fan percent.

High temperature threshold (°C)

20 to 80

Specifies the upper threshold of the temperature.

When the temperature exceeds this threshold, an alarm is reported.

Low temperature threshold (°C)

-40 to 10

Specifies the lower threshold of the temperature.

When the temperature is lower than this threshold, an alarm is reported.